UQD Series Products

Four sizes engineered for direct-to-chip liquid cooling. All models comply with OCP Specification Rev 1.0.

Available Configurations

The UQD Series includes standardized outer envelopes, coupling geometries, and performance criteria across all sizes.

02
UQD-02
Flow Coefficient 0.25 Cv
Fluid Loss/Cycle ≤0.020 ml
Operating Pressure 100 psi
Burst Pressure 300 psi
04
UQD-04
Flow Coefficient 0.65 Cv
Fluid Loss/Cycle ≤0.035 ml
Operating Pressure 100 psi
Burst Pressure 300 psi
06
UQD-06
Flow Coefficient 1.25 Cv
Fluid Loss/Cycle ≤0.050 ml
Operating Pressure 100 psi
Burst Pressure 300 psi
08
UQD-08
Flow Coefficient 2.50 Cv
Fluid Loss/Cycle ≤0.070 ml
Operating Pressure 100 psi
Burst Pressure 300 psi

Complete Specifications

All UQD Series couplings share common performance and material specifications per OCP Rev 1.0.

Performance Requirements

Parameter Specification Notes
Operating Pressure 100 psi (max) Continuous operation
Burst Pressure 300 psi (min) Safety factor 3:1
Operating Temperature 17°C to 65°C Coolant temperature range
Endurance Rating 5,000 cycles (min) Mechanical connect/disconnect
Leak Testing Pressure decay method Per qualification protocol

Material & Termination

Component Specification
Wetted Materials Compatible with DOWFROST™ LC25 and JEFFCOOL® ISF-25
Barbed Termination For EPDM tubing connection
Threaded Interface ORB per ISO 11926-1/-3
Surface Finish Sealed, no sharp edges or tool marks in wetted areas

Quality & Compliance

Standard Description
OCP UQD Specification Revision 1.0 — Full compliance
ISO 9001 Quality management system certification
ISO 11926-1/-3 Threaded port interface standard
IEC 62368-1 Clause G.15 Safety requirements

Validation Testing

Test Method
Mechanical Endurance 5,000-cycle connect/disconnect testing
Burst Test Hydrostatic pressure to failure
Leak Test Pressure decay method
Dimensional Validation CMM inspection against critical dimensions
Tolerance Analysis Stack-up analysis for interoperability

Need Technical Support?

Our engineering team can help you select the right configuration for your application.

Contact Engineering